C E N T A U R U S P R I M E
Click Transfer > Receive File: Enter the location to save the file and make sure that
Xmodem is selected and then click the Receive button. The next dialog box will ask
you to specify a filename and when you click “OK” the file will be received from the
Gateway.
Setting up the Modbus Driver
After the Gateway is ready to go and you have your database configured, one of the
last steps is to make sure that you have the Modbus driver settings for the
Host/Master setup correctly. The following information should be kept in mind when
configuring the driver
Modbus commands that are accepted by the Gateway are:
1 - Read Coils (0000's)
2 - Read Discretes (10000's)
3 - Read Holding Registers (40000's)
4 - Read Input Registers (30000's)
5 - Force Single Coil
6 - Preset Single Register
7 - Read Exception Status (Status is 0 if OK; o/w internal error-code)
15 - Force Multiple Coils
16 - Preset Multiple Registers
17 - Report Slave ID (Emulates Modicon Micro-84)
Most Modbus drivers have many setup options and each vendor is different. Following
are some limits with the Modbus Gateway that you need to consider when setting up
your driver.
MAXIMUM number of coils read at once (CMD #1) is 64
MAXIMUM number of discretes read at once (CMD #2) is 64
MAXIMUM number of holding registers read at once (CMD #3) is 32
MAXIMUM number of input registers read at once (CMD #4) is 32
MAXIMUM number of coils forced at once (CMD #15) is 8
MAXIMUM number of registers preset at once (CMD #16) is 8
TIMEOUT for a command should be a minimum of 350 milliseconds
(500 ms recommended)
TIME BETWEEN commands should be a minimum of 50 milliseconds
(100 ms recommended)
NUMBER OF TIMEOUTS before "slow polling" should be a minimum of
3 (3 recommended)