Cirrus Logic CS485 Spécifications Page 28

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 36
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 27
C E N T A U R U S P R I M E
25
2525
25
Field In / Out Counts : 0 / 0 Field Value : 0.000
Field Hi / Lo Range : 255.000 / 0.000 Eng. Units : Deg F.
And this is what is displayed for an example BACnet controllable object that has been
released from all controls (note the line that says “No elements in priority/control
array”:
CTL: (S)elect, (P)riority, (C)ontrol, (R)elease, (D)etail, (X)-it :D
BACnet Obj_ID 113, Type = AO, “Max Cooling Flow SPT”
No elements in priority/control array
Field Unit / Subunit : 4 / 0 Field Address :30001
Object Flags / Errors : 0 / 0
Field In / Out Counts : 0 / 0 Field Value : 0.000
Field Hi / Lo Range : 10000.000 / 0.000
Engineering Units : Percnt
Had any priorities have controls in them, it would have displayed the priority and the
control value, for EACH priority level.
SPECIAL NOTE FOR BO point #14 (Recalibration):
This point is, according to Trane, the “recalibration” point for a VAV box. It is
pathetically slow in acting. The Trane manual errata sheet says that you must control
the point ON for five minutes, then turn it OFF. The actual feedback from the point
does show ON, but only for about 20 seconds, so the feedback is fairly useless (and, in
fact, we suggest that you NOT define it!). However, the Trane documentation also
says that it takes up to 15 minutes to drive the damper full closed to do the calibrations.
It has been found that in real life, it takes sometimes 20 to 25 minutes to actually do
the physical damper motion and recalibration. Have patience!
Watch Menu Options
The “Watch menu will let you select various methods for monitoring the real time
data from the field.
(Q)uiet: Use the (Q) key to halt any of the following monitoring options.
(1),(2),(3),(4) to Watch Trunks: Enter a Trane VAV trunk to monitor. This will display
the field scan of all Trunk devices and the status of their points in real time. What is
displayed below is the Modbus variant (it shows the register numbers in the second
column); the BACnet variation is the same except it shows the BACnet object
instances in the second column: