5 / 2 0 0 6 V E R S I O N 1 . 1 CENTAURUS PRIME Integrations, Custom Programming, Consulting Trane-485 Gateway Guide

Page 2 - Trane-485 Gateway Guide

C E N T A U R U S P R I M E 7777 RS422 Communications Installed jumpers: Baud0, Baud1, Data DCD, Data RTS, J2 (end of line only), J3 (end of lin

Page 3 - Table of Contents

C E N T A U R U S P R I M E 8888 NOTE about removing the CS-485: For RS-232 or Ethernet applications, the CS-485 module is not used, and

Page 4 - Basic Information

C E N T A U R U S P R I M E 9999Gateway Overview Picture 1.3, Gateway Overview and Identification Trane Trunk 4 1 Amp Fuse Remove Cover for Po

Page 5 - Single Board Computer Basics

C E N T A U R U S P R I M E 10101010Commissioning the Gateway with the Local User Interface Creating and Downloading the GATEWAY.INI file The foll

Page 6

C E N T A U R U S P R I M E 11111111MUST match! If the SOCKET.CFG specifies a different IP address from the GATEWAY.INI file, you wil

Page 7

C E N T A U R U S P R I M E 12121212// -------------------------------------------------------------------------- // // “BACNET_NETWORK” is used

Page 8 - Configuring the CS485

C E N T A U R U S P R I M E 13131313Local Mode Menu Options Once connected via the local mode port you may press <enter> at any time to disp

Page 9 - RS485 Communications

C E N T A U R U S P R I M E 14141414State: "AutoDiscovery" on Trunk: 1, VAV Device #5 State: "AutoDiscovery" on Trunk: 1, VA

Page 10

C E N T A U R U S P R I M E 15151515AUTODISCOVERY: You may SAVE and MERGE all trunk auto-discovery maps. ARE YOU SURE? If so, enter "

Page 11

C E N T A U R U S P R I M E 16161616TagID: "VAV#4, TRUNK 1 (MB #1)" is ON-LINE & RELIABLE TagID: "VAV #1, TRUNK 2 (MB #61)"

Page 12 - Gateway Overview

5 / 2 0 0 6 V E R S I O N 1 . 1 I N T E G R A T I O N S , C U S T O M P R O G R A M M I N G , A N D C O N S U L T I N G Trane-485 G

Page 13 - User Interface

C E N T A U R U S P R I M E 17171717(A)ll: View all configured devices. DEV: (S)elect, (A)ll, (D)etail, (O)ff-line, (C)omm Stats, (X)-it :A

Page 14

C E N T A U R U S P R I M E 18181818TagID: "VAV #4, TRUNK 1 (MB #1)" statistics: Packets Today: 463 RX Errors Today: 0

Page 15

C E N T A U R U S P R I M E 19191919 MB Reg 10011 (DI) "Damper Forced Closed " Fld: 0 NORMAL (0-state) MB Reg 10012

Page 16 - Local Mode Menu Options

C E N T A U R U S P R I M E 20202020 BACnet ID 8 (AI) "Damper/Valve Pos " Fld: 24 ==> 24.00 BACnet ID 9 (

Page 17

C E N T A U R U S P R I M E 21212121PNT: You may select an OBJECT ID to target into. Enter a valid, existing, Object ID (1 to 49999) : 3000

Page 18 - “Summary” Menu Options

C E N T A U R U S P R I M E 22222222Now, before you can control a point object you must first have selected a device number and point

Page 19 - “Devices” Menu Options

C E N T A U R U S P R I M E 232323236 Minimum On/Off Trane: Miscellaneous 7 Custom Programming—High Trane: Demand Limiting 8 Manual Operator Trane

Page 20

C E N T A U R U S P R I M E 24242424 (P)riority: (BACnet ONLY) Use this to select the priority that you will issue subsequent contr

Page 21 - “Point” Menu Options

C E N T A U R U S P R I M E 25252525 Field In / Out Counts : 0 / 0 Field Value : 0.000 Field Hi / Lo Range : 255.000 / 0.000 En

Page 22

C E N T A U R U S P R I M E 26262626WCH: (Q)uiet, (1),(2),(3),(4) to watch trunks; (V)erbose, (M)odbus, (X)-it :1 *** TRUNK 1 is now being MONIT

Page 23

Table of Contents Introduction i C H A P T E R 1 Gateway Installation, Basic Information 1 Summary 1 Single Board Computer Basics 2 Connectin

Page 24 - “Control” Menu Options

C E N T A U R U S P R I M E 27272727AI 30003 Active Cooling SP Used Counts: 76 = 76.00 AO 40004 OCCUPIED Heating SPT Counts: 71 =

Page 25

C E N T A U R U S P R I M E 28282828 Receiving a file from the Gateway (downloading) From the dos prompt, you must type “DOWN filename” (filenam

Page 26

C E N T A U R U S P R I M E 29292929Click Transfer > Receive File: Enter the location to save the file and make sure that Xmodem is selected an

Page 27

C E N T A U R U S P R I M E 30303030Setting up the BACnet System After the Gateway is ready to go and you have your database configured, one of t

Page 28 - “Watch” Menu Options

C E N T A U R U S P R I M E 31313131Modbus & BACnet Point Mapping Device Point Mapping for VAV-1s and VariTranes Monitor Control Older (VAV-

Page 29

C E N T A U R U S P R I M E 3232323210014 / 314 14 / 414 Min. Setpoint Forced Maximum Heating Forced 0=AUTO; 1=FORCED 10015 / 315 15 / 415 Ma

Page 30

33333333 Index (A)larms, 15, 16 (C)ontrol, 13, 14, 22, 24 (C)ontrolled, 15, 16 (D)etail, 17, 18, 19, 20, 21, 22, 24, 25 (D)evices, 15 (H)elp

Page 31

C E N T A U R U S P R I M E 1111 Gateway Installation Basic Information Summary his section will help to give a basic overview and quick

Page 32

C E N T A U R U S P R I M E 2222configuration. Single Board Computer Basics The Single Board Computer used in Centaurus Prime Gateways is the Eth

Page 33

C E N T A U R U S P R I M E 3333Connecting Power to the Gateway Power connections are made by removing the 2 screws on either side of the terminal

Page 34 - Mapping

C E N T A U R U S P R I M E 4444avoid ground-loops). This is a two-wire trunk, so it does not matter if you land the field trunk wires on TX+/TX-

Page 35

C E N T A U R U S P R I M E 5555device to reliably transmit data over long distances (up to 4000 feet). The CS485 has many features not normally f

Page 36 - Serial Port, 2

C E N T A U R U S P R I M E 6666 OUT Enables 4-wire operation RX is receive pair TX is transmit pair J15 Connects isolated RS-485 commo